Display LCD
Indication PASS/FAIL and Measured Values
Operation 6 Push Button
INSULATION TEST
Test Range 500V DC, 1Mohm at rated mains supply
Pass Level 1Mohm
EARTH CONTINUITY TEST
Test Current 200mA
Pass Level 1ohm
LEAKAGE TEST
Output Voltage 240V AC
Pass Level Class I 5mA, Class II 1mA
MOV DEVICES LEAKAGE TEST
Output Voltage 240V AC
Pass Level Class I 5mA, Class II 1mA
EXTENSION LEAD LEAKAGE TEST
Pass Level 1mA
POLARITY TEST
Pass Indication live/neutral open circuit, short circuit and crossed connections
RCD TRIP TIME TEST
Test Current 10mA/30mA
Test Current Phase 0o/180o auto switched
Display Range 0ms – 500ms
Pass Value 10mA RCD 40ms, 30mA RCD 300ms
Portable & Fixed RCDs
In-Built Isolation Transformer
3 PHASE LEAKAGE TEST
Test Voltage 415V
Pass Value 5mA
POWER SOCKET TEST
Input Voltage Range 255 – 254V AC
Indicators Live to earth voltage, Live to neutral voltage, Neutral to earth voltage
INTERFACES
USB for data download in CSV file format for any spreadsheet or database program
Serial for connection to PAC-OPT OPTIMA test tag printer
On-Board Memory 999 test results
Weight 0.8kg
Dimensions 26cm x 10cm x 5.5cm
Power Source 6 x AA batteries
Accessories padded carry case, earth bond clip, IEC adaptor, mains supply test lead
Optional Accessories
PAC-OPT OPTIMA test tag printer
PAC-TPL 3 phase leakage test adaptor